| IEC Electrical | 150 | 275 | 320 | 385 | 440 | ||
| Nazivna AC napetost (50/60Hz) | 120V | 230V | 230V | 230V | 400V | ||
| Največja neprekinjena delovna napetost (AC) | (LN) | Uc | 150V | 275V | 320V | 385V | 440V |
| (N-PE) | Uc | 255 V | |||||
| Nazivni izpustni tok (8/20μs) | (LN)/(N-PE) | In | 20kV/20kA | ||||
| Največji tok praznjenja (8/20 μs) | (LN)/(N-PE) | Imax | 40kA/40kA | ||||
| Raven napetostne zaščite | (LN)/(N-PE) | Up | 1,0kV/1,5kV | 1,5kV/1,5kV | 1,6kV/1,5kV | 1,8kV/1,5kV | 2,0kV/1,5kV |
| Sledite trenutni oceni prekinitev | (N-PE) | Če jaz | 100ARMS | ||||
| Odzivni čas | (LN)/(N-PE) | tA | <25ns/<100ns | ||||
| Rezervna varovalka (maks.) | 125A gL /gG | ||||||
| Nazivni tok kratkega stika (AC) | (LN) | ISCCR | 20kA / 50kA | ||||
| TOV Vzdrži 5s | (LN) | UT | 180V | 335V | 335V | 335V | 580V |
| TOV 120min | (LN) | UT | 230V | 440V | 440V | 440V | 765V |
| način | Zdrži | Safe Fail | Safe Fail | Safe Fail | Safe Fail | ||
| TOV vzdrži 200ms | (N-PE) | UT | 1200V | ||||
| Območje delovne temperature | -40ºF do +158ºF [-40ºC do +70ºC] | ||||||
| Dovoljena delovna vlažnost | Ta | 5 %…95 % | |||||
| Atmosferski tlak in nadmorska višina | RH | 80k Pa..106k Pa/-500m..2000m | |||||
| Navor vijaka sponke | Mmax | 39,9 lbf-in [4,5 Nm] | |||||
| Prerez vodnika (maks.) | 2 AWG (polna, pletena) / 4 AWG (prilagodljiva) | ||||||
| 35 mm2 (polna, vijačna) / 25 mm2 (prilagodljiva) | |||||||
| Montaža | 35 mm DIN letev, EN 60715 | ||||||
| Stopnja zaščite | IP 20 (vgrajen) | ||||||
| Material ohišja | Termoplast: Stopnja gašenja UL 94 V-0 | ||||||
| Toplotna zaščita | ja | ||||||
| Indikacija stanja delovanja/napake | Zelena v redu / rdeča okvara | ||||||
| Oddaljeni kontakti (RC) / RC preklopna zmogljivost | Neobvezno | ||||||
| Prerez RC vodnika (maks.) | AC: 250 V/0,5 A; DC: 250 V/0,1 A; 125 V/0,2 A; 75 V/0,5 A | ||||||
| 16 AWG (polno) / 1,5 mm2 (polno) | |||||||